<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Archiving and Interchange DTD v1.0 20120330//EN" "JATS-archivearticle1.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <journal-meta />
    <article-meta>
      <title-group>
        <article-title>Systems for Monitoring Modes and Disturbances in High- Voltage Transmission Lines</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>Yuriy Franko</string-name>
          <email>franko@tnpu.edu.ua</email>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <contrib contrib-type="author">
          <string-name>Julia Franko</string-name>
        </contrib>
        <aff id="aff0">
          <label>0</label>
          <institution>. Department of Computer Technologies, Ternopil Volodymyr Hnatiuk National Pedagogical University, UKRAINE</institution>
          ,
          <addr-line>Ternopil, 10</addr-line>
        </aff>
      </contrib-group>
      <pub-date>
        <year>2018</year>
      </pub-date>
      <fpage>1</fpage>
      <lpage>3</lpage>
      <abstract>
        <p>The article is devoted to the important practical task of using computerized systems of monitoring and control objects of electric power engineering, in which arise problems associated with the effectively identify abnormal situations in high-voltage electrical networks..The effectiveness of applying computerized monitoring systems to control electric power objects is substantiated. The structures and components of control and diagnostics systems for monitoring modes, recognition and authentication of disturbances in high-voltage transmission lines of 6-35 kV are studied. The "Strila" and "Altra's" functions are systematized as the network components of automated remote monitoring and controlling the technological equipment of electric substations. A sequence of operations for the recognition and authentication of load surge, earth fault and starting up powerful electric motors in high-voltage transmission lines is formalized. A structure and components of a microelectronic specialpurpose processor protection relay of high-voltage transmission lines are presented.</p>
      </abstract>
    </article-meta>
  </front>
  <body>
    <sec id="sec-1">
      <title>I. INTRODUCTION</title>
      <p>
        One of the main tasks of electricity supply is the
maintenance of equipment in an operational condition.
Therefore, using new methods for diagnosing the technical
condition using specialized microcontrollers and special
processors with a high level of digital signal processing is
one of the most actual tasks..The successful development of
microprocessor and microelectronic technology has created
favorable conditions for the development and large-scale
replication of automated monitoring distributed computer
systems (DCS) to monitor and control distant technological
facilities in various industries. The examples of the succesful
application of the SCADA systems of this class are the
developments made by famous foreign firms and domestic
enterprises, for example, Oven, Elektrosvit, Schneider, etc.
[
        <xref ref-type="bibr" rid="ref1 ref2 ref3 ref4">1-4</xref>
        ]. The DCSs [
        <xref ref-type="bibr" rid="ref5 ref6">5-6</xref>
        ] designed and developed by Ternopil
design bureau (TDB) "Strila" and the Institute of
microprocessor control systems of electric power objects
(IMCSPEO, Lviv) are being effectively introduced into the
electric-power industry. These information systems are
multifunctional, and embrace a wide spectrum of functions:
monitoring, authentication of and controlling the equipment
of 6-35-kV electric substations.
      </p>
      <p>The important condition for permanent expansion of the
functional capabilities, improvement of the system
characteristics, and perfection of the components is their
being equiped with specialized microcontrollers and
specialpurpose digital signal processors. First of all, it concerns the
recognition and authentication of disturbances in
highvoltage transmission lines in case of load surge, short-term
cable fault, earth fault and starting up powerful electric
motors, for example, in the oil and gas industry. The
theoretic base of the algorithms for digital signal processing
of phase currents and voltages in case of transients and
transmission line disturbances in is formed by the image
recognition methods, as well as by the statistical,
correlational, spectral, and entropy analysis.</p>
    </sec>
    <sec id="sec-2">
      <title>II. AUTOMATED REMOTE-CONTROL SYSTEM (ARCS) "STRILA"</title>
      <p>
        The ARCS developed by the TDB "Strila" [
        <xref ref-type="bibr" rid="ref5">5</xref>
        ] is
designed for remote control, collection of telesignallization
and telemetering parameters at 6-35-kV electric substations.
      </p>
      <p>A control point (CP) of the "Strila" telemetry executes
previous signal processing of phase voltages and currents,
archive registration of digital data, and transmission of coded
messages to a distant dispatching point (DP) of the district
electric grid (DEG). In addition, the CP receives and
executes the commands remotely passed from the DP.</p>
      <p>The basic structure of the operative-information complex
"Strila", which belongs to the class of the SCADA systems,
consists of two remote modules, which are installed at the
substation of 35/10 kV, and a server hosted in the offices of
dispatching services of DEG and Oblenergo.</p>
      <p>The structure of the control point at the 35/10 kV
substation is shown in Fig. 1.</p>
      <p>Fig. 1. Structure of CP : 1 - telesignallization module; 2 –
telemonitoring module; 3 - telecontrol module; 4 - processor
(microcontroller); 5 – operator’s keyboard; 6 - radiomodem
The CP has the following information characteristics:
512 (32х16) discrete inputs (ТS);
256 (16х16) analogue inputs (ТV);
128 (16х8) control objects (ТU);
RS-485 – master interface up to 2000 М;
МЕК 870-5-101 – protocol of a code interaction between
CP and DP.</p>
      <p>While operating, the CP performs a component
diagnostics and transmits information to DP. The structure of
the "Strila" server equipment at DEG is shown in Fig. 2.</p>
      <p>The DP’s server hardware of the complex "Strila" that is
located at DEG executes:
3G CDMA EV-DO – safety system software;
IEC 60870-5-101 – computer network protocols;</p>
      <p>IEC 60870-5-104 – integration with server equipment of
the top-level electricity company CRM "UDS Consulting"
(Call-centre) with a direct transfer of information on the
position of energy facility switches.</p>
      <p>The server system of DEG executes:
- graphic representation of tables of current, voltage and
power of connections at the controlled electric substations;
- registration of system events (telecontrol, queries,
program states, channel diagnostics, etc.);</p>
      <p>- controlling the mimic diagram board, indexation of
switch position and alarm system.</p>
      <p>The described structure and functionality of the system
"Strila" indicate that its level of microelectronic equipment
and software meets the world’s existing problem-oriented
information systems of the SCADA class that are produced
by leading foreign firms in the field of electricity.</p>
      <p>At the same time, the classic reflection of the states of
technological equipment at electric substations in the form of
time trends, and tabular representation of digital data on the
controlled parameters and processes greatly complicate the
interaction of system operators, significantly reduce the
speed and effectiveness of their responses to abnormalities
of the states of technological facilities both before and at
emergency. In addition, the system "Strila", as well as other
systems of this class, is not intended to and does not carry
out a deep statistical, correlational, spectral and entropy
processing of telemetering signals with the possibility of
recognition and authentication of disturbances in
highvoltage transmission lines at invariant values of phase
currents and voltages. For example, in case of load surge and
start-up of powerful electric drives, starting phase currents
can considerably exceed those of earth-faults at a
considerable distance from the substation’s switching
equipment with certain adjustments of relay protection
facilities.</p>
      <p>Such functions may be implemented successfully by
specialized microelectronic processors on PLIS or by
expansion of the problem orientation of application software
of the computers embedded in such systems. In addition, the
high performance of the special-purpose processors
accelerating the signal processing by 1-2 orders of magnitude
in comparison with the universal ones used in
multifunctional microcontrollers allows the industrial
equipment of power systems to be effectively and reliably
secured on the intervals of 1-2 periods of industrial
frequencies.</p>
      <p>III. CONTROL AND DIAGNOSTICS SYSTEM
"ALTRA</p>
      <p>MINI-ALTRA"</p>
      <p>
        The system "Altra" developed by IMCSPEO [
        <xref ref-type="bibr" rid="ref6">6</xref>
        ] carries
out local and distance monitoring of the insulation state of a
6-35 kV electric grid of arbitrary configuration with an
insulated or compensated neutral. It performs a continuous
real-time monitoring of the state of connections isolation at
an electric substation, detection of a damaged area and its
localization.
      </p>
      <p>The system "Altra" performs the following functions:
- registration of partial insulation failure of arbitrary
duration that provides the insulation state diagnostics of
network segments;</p>
      <p>- detection of an electric network segment with thinned
insulation, remote transfer of information on its mode
coordinates to the dispatching point;</p>
      <p>- bay disconnection by single- phase earth fault
protection, ensuring the appropriate selectivity depending on
its kind, duration, category of consumers, features of
insulants;</p>
      <p>- displaying a network map on the monitor of the
dispatching point, authentication of a thinned insulation
segment;</p>
      <p>- remote control of the substations’ switching facilities
by using the switchgears equipped with appropriate drives.</p>
      <p>The system "Altra-Mini-Altra" is built on the multilevel
principle where "Altra" and "Mini-Altra" are the basic
blocks. "Altra" is installed at the substations and distribution
points of 6-35 kV for the purpose of detection and
registration of monophase earth faults. The device is
designed for servicing up to 12 connections; the chart of its
connections is shown in Fig.3.</p>
      <p>Information for the "Altra" device is the phase voltages
ua, ub, uc and the value of the voltage of the zero sequence
of 3u0, which are obtained from the sectional voltage
transformer, as well as currents of zero sequence, which are
obtained from current transformers of zero sequence of
connections. Overall dimensions of the device are 40x30x22
cm. The device "Altra" can be installed on the facades of
standard panels, as well as on its free parts or directly on the
walls of the substation building or at the distribution
substations. If necessary, to have information about the
position of the switching devices, the device "Altra" is
supplemented by a block of control the state of discrete
signals.
voltage control at separate substations takes place on the
basis of information received both from "Altra" and
"MiniAltra". Therefore, these devices are provided with 1 ms
timing according to GPS–technology.</p>
      <p>The data collection functions are performed by the
concentrator based on the embedded computer.</p>
      <p>The block diagram of data collection executed by the
information system "Altra" is shown in Fig. 6.
The block diagram of the "Altra" concentrator is shown
in Fig. 4.
"Altra" responds to the earthing of a connection phase.
At any duration of the phase earthing, the date and time of
the event when an insulation breakdown, and effective
current of zero-phase sequence are detected can be seen on
the "Altra’s" display. Digital graphs of all mode coordinates
are recorded in the power independent memory. The position
of switching equipment is monitored by a block intended for
monitoring the state of discrete signals. For the selective
detection of a network segment with thinned insulation, the
substations without voltage control are equipped with
"MiniAltra" devices (Fig. 5).</p>
      <p>This device controls the current of a zero sequence of
substation connections (8 connections). The detection of a
thinned insolation segment of the network with partly</p>
      <p>
        The improvement of the "Altra’s" software and
hardware, and the expansion of its functional capabilities is
realized by reequipping the system with special-purpose
processor protection relay of high-voltage transmission lines,
whose structure is shown in Fig. 7 [
        <xref ref-type="bibr" rid="ref6 ref7 ref8 ref9">6-9</xref>
        ]. This is done on the
basis of theoretical and experimental studies of transient
processes in the transmission lines in case of charges and
short circuits.
      </p>
      <p>The basis of the structural solution of this device is the
task of improving the protection relay of high-voltage
transmission lines by introducing a current rectifier, an
analogue-to-digital converter, a logic element "Excluding
OR", and a shift register. This makes it possible to recognize
charges and short circuits in the transmission line, regardless
of the absolute values of current growth in one of the phases.</p>
      <p>The main advantages of the proposed relay protection
device for high-voltage transmission lines are: advanced
functionality; high speed recognition of charges and short
circuits at intervals of one - two periods of industrial
frequency; simplified algorithm of microelectronic
implementation of the device; possibility of realization on a
FPGA crystal; reduced cost of the device and the possibility
of mass replication and implementation at high-voltage
substations; increased reliability and ability to work in a
wide range of temperatures.</p>
      <p>
        The device operation based on the method of
integraldifference processing of phase currents in case of
disturbances in high-voltage transmission lines developed by
IMCSPEF in collaboration with the Department of
specialized computer systems of Ternopil National
Economic University [
        <xref ref-type="bibr" rid="ref10 ref8">8,10</xref>
        ].
      </p>
      <p>Figure 8 shows an example of a change in the
characteristics of digital graphs of a phase current at load
surge (1), earth-faults (2) and starting up powerful electric
drives (3).</p>
      <p>The results of computer modeling and identification of
classified load surge (perturbations) in transmission lines are
shown in Fig. 9, namely, integral characteristics of the
modular differences in the squares of instantaneous current
values of working and output currents, in the case of
threephase drives (the start of powerful electric motors). In
particular, starting the powerful asynchronous motors, and
long-term start-ups are shown in Fig.9.</p>
    </sec>
    <sec id="sec-3">
      <title>IV. CONCLUSION</title>
      <p>The actuality and effectiveness of applying computerized
systems of monitoring and control of electric power
engineering objects is outlined. The functions and basic
modules of the structures of "Strila" and "Altra" are
systematized. The necessity of expanding functional
capabilities of the systems of such class by using
microelectronic special-purpose processors with a deep level
processing of digital graphs of phase currents on the basis of
statistical, cross-correlation, spectral and entropy analyses is
substantiated.</p>
      <p>The structure of the relay protection device based on the
microelectronic special-purpose processor was designed and
the results of computer simulation of the proposed
integraldifference method of the correlation signal processing in case
of disturbances in high-voltage transmission lines are
presented. Such devices can widely be used both as the
components of computerized systems for monitoring and
control of the electric substations equipment and autonomous
specialized protection relays. The control and diagnostic
monitoring systems allow to effectively identifying abnormal
situations in high-voltage electrical networks.</p>
    </sec>
  </body>
  <back>
    <ref-list>
      <ref id="ref1">
        <mixed-citation>[1] Electronic resource: https: // www.abb.ua</mixed-citation>
      </ref>
      <ref id="ref2">
        <mixed-citation>[2] Electronic resource: http://elektrosvit.com.ua</mixed-citation>
      </ref>
      <ref id="ref3">
        <mixed-citation>[3] Electronic resource: https://owen.ua</mixed-citation>
      </ref>
      <ref id="ref4">
        <mixed-citation>[4] Electronic resource: https:// schneider-electric.ua</mixed-citation>
      </ref>
      <ref id="ref5">
        <mixed-citation>[5] Electronic resource: http: // tkbr-strila@ukr.net</mixed-citation>
      </ref>
      <ref id="ref6">
        <mixed-citation>[6] Electronic resource: http://imskoe.org.ua</mixed-citation>
      </ref>
      <ref id="ref7">
        <mixed-citation>
          [7]
          <string-name>
            <given-names>Oleh</given-names>
            <surname>Liura</surname>
          </string-name>
          , Ivan Ostrovka, Iryna Sabadash, Yaroslav Nykolaichuk,
          <article-title>"Theoretical Principles and Methods of Disturbances Recognition in Load Surges"</article-title>
          ,
          <source>in Proc. Modern Problem of Radio Engineeriong</source>
          , Telecommunikations and Computer Science: TCSET'
          <year>2016</year>
          , pp.
          <fpage>33</fpage>
          -
          <lpage>36</lpage>
          , Slavske in Lviv region, Ukraine,
          <year>2016</year>
          .
        </mixed-citation>
      </ref>
      <ref id="ref8">
        <mixed-citation>
          [8]
          <string-name>
            <given-names>Y.M.</given-names>
            <surname>Nykolaichuk</surname>
          </string-name>
          ,
          <string-name>
            <given-names>N.Y.</given-names>
            <surname>Vozna</surname>
          </string-name>
          ,
          <string-name>
            <given-names>O.P.</given-names>
            <surname>Liura</surname>
          </string-name>
          ,
          <string-name>
            <surname>I.I. Ostrovka</surname>
          </string-name>
          , І.І. Sabadash,
          <article-title>Protection relay of high-voltage transmission lines</article-title>
          ,
          <source>Ukraine Patent № 103938</source>
          ,
          <year>2016</year>
          , Bull. №
          <volume>1</volume>
          (in Ukrainian).
        </mixed-citation>
      </ref>
      <ref id="ref9">
        <mixed-citation>
          [9]
          <string-name>
            <given-names>O.P.</given-names>
            <surname>Liura</surname>
          </string-name>
          ,
          <string-name>
            <given-names>N.Y.</given-names>
            <surname>Vozna</surname>
          </string-name>
          ,
          <article-title>"Research into and optimization of component characteristics of a microelectronic protection relay of high-voltage transmission lines"</article-title>
          ,
          <source>in Proc. Scientific Bulletin of UNFU of Ukraine</source>
          , pp.
          <fpage>6</fpage>
          -
          <lpage>12</lpage>
          , Vol.
          <volume>27</volume>
          . № 5,
          <string-name>
            <surname>Lviv</surname>
          </string-name>
          ,
          <year>Ukraine 2017</year>
          . (Ukrainian)
        </mixed-citation>
      </ref>
      <ref id="ref10">
        <mixed-citation>
          [10]
          <string-name>
            <surname>Tetiana</surname>
            <given-names>Zavediuk</given-names>
          </string-name>
          , Yurii Franko, Oleg Liura, Ivan Ostrovka,
          <article-title>"Methods of Recognition and Identification of disturbances in High-Voltage Power Lines"</article-title>
          ,
          <source>proceedings of the XIII th International Conference CADSM</source>
          <year>2015</year>
          ,
          <article-title>Lviv-</article-title>
          <string-name>
            <surname>Polyana</surname>
          </string-name>
          , Lviv Poliytechnic Publishing House, Ukraine,
          <year>2015</year>
          , pp.
          <fpage>282</fpage>
          -
          <lpage>285</lpage>
          .
        </mixed-citation>