<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Archiving and Interchange DTD v1.0 20120330//EN" "JATS-archivearticle1.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <journal-meta>
      <journal-title-group>
        <journal-title>October</journal-title>
      </journal-title-group>
    </journal-meta>
    <article-meta>
      <title-group>
        <article-title>MODERNIZATION OF THE MANAGEMENT AND CONTROL SYSTEM FOR THE COLD NEUTRON MODERATOR AT THE FAST PULSED REACTOR</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>A.V. Altynov</string-name>
          <email>altynov@jinr.ru</email>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <contrib contrib-type="author">
          <string-name>M.V. Bulavin</string-name>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <contrib contrib-type="author">
          <string-name>A.P. Sirotin</string-name>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <aff id="aff0">
          <label>0</label>
          <institution>JINR</institution>
          ,
          <addr-line>6 Joliot-Curie st., Dubna Moscow Region, 141980</addr-line>
          ,
          <country country="RU">Russia</country>
        </aff>
      </contrib-group>
      <pub-date>
        <year>2019</year>
      </pub-date>
      <volume>4</volume>
      <issue>2019</issue>
      <fpage>290</fpage>
      <lpage>294</lpage>
      <abstract>
        <p>The management and control system of the cold neutron moderator allows the engineering staff to monitor, in the process of its operation, the main parameters of the moderator, including the gas blower rotation speed, the consumption and temperature of helium, the vacuum in the jacket and the passage of pellets in the transport pipe. Today, complex upgrading of the cold neutron moderator at the fast pulsed reactor "IBR-2M" is underway. The paper presents the current version of the structure of the management and control system for the cold moderator. Interface convertors are used to connect the management and control equipment of the cold moderator to the computer. The main interface of the data acquisition and control system of the executive devices is RS-485. Specialized software has been created to operate the management and control system of the cold neutron moderator.</p>
      </abstract>
      <kwd-group>
        <kwd>IBR-2</kwd>
        <kwd>cold neutron moderator</kwd>
        <kwd>modernization</kwd>
      </kwd-group>
    </article-meta>
  </front>
  <body>
    <sec id="sec-1">
      <title>-</title>
      <p>1.</p>
    </sec>
    <sec id="sec-2">
      <title>History of the moderator</title>
      <p>In the 80s of the last century, the idea of a bulk neutron moderator using ice and methane was
first proposed, but it could not be realized because of the low radiation resistance of these materials.</p>
      <p>
        Later, at the end of the last century, while studying the radiation properties of
hydrogencontaining materials, it was found that mesitylene is destroyed 20 times slower than methane and
absorbs neutrons three times less than methane. So, the idea of creating a neutron moderator with the
use of mesitylene in a helium medium appeared [
        <xref ref-type="bibr" rid="ref1">1</xref>
        ]. In 2005 project work on the pelletized cold
neutron moderator started. Research on specific features of the pneumatic transport of mesitylene
pellets in helium was carried out parralelly. Specialists of the Central Aerohydrodynamic Institute
were involved in choosing the optimal mode. They selected an optimal mode for transport of pellets in
the system allowing them to overcome the rises. The cryogenic system and the optimal size of the
pellets were developed.
      </p>
      <p>
        In 2011 development of the project was completed, and in 2012 the moderator was firstly
launched. In 2013 the moderator was put into operation [
        <xref ref-type="bibr" rid="ref2">2</xref>
        ].
2. Control system
•
•
•
•
•
•
      </p>
      <p>The moderator control system consists of the following main subsystems:</p>
      <sec id="sec-2-1">
        <title>Control and management system of the dosing machine; Temperature control system for individual units; Pressure monitoring system in the moderator circuit. The main areas of modernization of the moderator control system are:</title>
      </sec>
      <sec id="sec-2-2">
        <title>Improving the reliability of the control system; Increasing the level of automation of the control system; Integration of new elements into the control system. Figure 1. The moderator control system</title>
        <p>The control system of pellets’ transport is based on the pressure difference during the passage
of pellets between two points in the pipeline. The DXLdp differential pressure measuring device
records the difference in pressure before and after the passing pellet. This allows to register the pellet,
to determine the speed of its movement. There are three differential pressure sensors in the system.
The first measures the gas flow during the operation of the facility. The gas flow rate is averaged per
second, to get rid of the high-frequency noise. Other sensors record the passage of pellets: the first
registers the passage of pellets into the system immediately after the dosing machine; the second
registers the passage of pellets on the rise and the lack of congestion control before the rise.</p>
        <p>Differential pressure sensors, in the process of modernization, are replaced by optical span
sensors Smart Fiber Amplifier Unit E3NX-FA11 allowing to record the passage of pellets at a high
rate.</p>
        <p>Data from pressure sensors are received by LA-20USB ADC (LA-20USB is multifunction
board analog-to-digital conversion for IBM PC) in real time, buffered and sent in packets via a USB
connector to a PC. In this case, the frequency of measurements on pressure sensors is 1 ms, the control
program survey is at a maximum rate of 1 s.</p>
        <p>The dosing machine is driven by stepper motors. About three hundred pellets are loaded at a
time. The stepper motor control system includes: a USB-CAN2 adapter with galvanic isolation to form
a CAN communication interface link for connecting a PC to stepper motor controllers, a KSMC-8
stepper motor main controller with galvanic isolation on the CAN link and optical isolation on the
limit switch monitoring circuits mounted in control cabinet.</p>
        <p>For work with KSMC-8 the standard MidStepTest software module is used to set the following
parameters of the engine operation:
 Velocity and direction of rotation;
 Current control modes in coils;



</p>
      </sec>
      <sec id="sec-2-3">
        <title>Magnitude of the operating current and retaining current;</title>
      </sec>
      <sec id="sec-2-4">
        <title>Minimum and maximum velocity;</title>
        <p>Acceleration (in rotation mode for a given number of steps);</p>
      </sec>
      <sec id="sec-2-5">
        <title>Processing modes of limit switches.</title>
        <sec id="sec-2-5-1">
          <title>2.2 Temperature control system for individual units</title>
          <p>The complex system of sensors includes 6 K-type thermocouples, a platinum resistance
thermometer for measuring the temperature of the cold junction and a silicon diode for high-precision
measurement of cryogenic temperature.</p>
          <p>Measurements are carried out using Keithley 2000 high-precision multivoltmeter with a
twenty-channel scanning card. Thermocouples are connected via a 2-wire circuit, the thermodiode and
the platinum thermometer - via a 4-wire circuit (a current of 10 µA for a Keithley resistance
thermometer and 50 µA for a thermodiode from an additional LakeShore 102 Current Source are
supplied through two wires). Voltage and resistance are measured differentially over two wires; the
other pair of wires (with a four-wire circuit) serves as power for the sensor current.</p>
          <p>Temperature is displayed in real time on the front panel of the display Keithley and is also
transmitted via the RS232 interface (again using the MOXA UPort1400 interface converter) to the PC.
During operation, we had to abandon the previously used multi-channel interface converter MOXA Uport
due to regular problems with the numbering of COM ports on the operator’s PC. Instead, a multi-channel
USB hub is used.</p>
          <p>The measurement accuracy is 0.002% for DC voltage and 0.008% for resistance.</p>
          <p>Software processing of the received data (with high-precision measurement of the reference
junction temperature) allows to get an error of not more than ± 1K.</p>
          <p>All information on the temperature is displayed both in numerical and graphical forms in PC
and is saved to a text file at the request of the user. The operating temperature in the moderator circuit
is about 30 K.</p>
        </sec>
        <sec id="sec-2-5-2">
          <title>2.3 Pressure monitoring system in the moderator circuit</title>
          <p>The vacuum control system in the moderator circuit includes eight MKS925 pressure sensors
and one MKS901 sensor.</p>
          <p>Also, during modernization of the moderator, 16 valves of the vacuum system were changed
from manual ones to electromagnetic. The valve solenoid is controlled via the 24 V line through the
OWEN relay block from the operator's PC. When the moderator is operating, the system pressure is
controlled programmatically and a ban is issued on changes in the state of the sensors, which can lead
to an emergency.</p>
          <p>The vacuum sensors MKS925 and MKS925 are designed for measuring pressure in the range
from 1×10−8 to 3000 Torr, at normal atmospheric pressure. The MKS925 sensors measure pressure
in the moderator circuit in the range of 1×10−4 Torr in the operating mode of the vacuum control
system. MKS901 sensors measure pressure close to normal atmospheric pressure, being reference
sensors for amending the readings of the MKS925 vacuum sensors.</p>
          <p>During operation and modernization of the cold moderator, the MKS925 sensors were
replaced with sensors of the same type of the later series with an improved electronic base and an
enlarged display, which reduced the number of failures.</p>
        </sec>
      </sec>
    </sec>
    <sec id="sec-3">
      <title>3. Software</title>
      <p>
        The SCP software package has been developed for the use of the moderator [
        <xref ref-type="bibr" rid="ref3">3</xref>
        ]. It includes six
modules:
 database server – VarmanServer;
 driver of the vacuum sensors MKS-901 and MKS-925 - d_press;
 temperature sensor driver - d_termo;
 gas holder driver - d_gasholder;
 driver of the frequency drive of the gas blower control system - d_freq;
 LA20-USB ADC driver - d_LA20;
as well as two main user interfaces:
• BMC to control the loading and movement of mesitylene pellets and gas flow;
• CM_Viewer to obtain information on the operation of cryogenic moderator systems.
•
•
•
•
•
•
•
•
•
•
      </p>
      <p>The software package is designed for the automation of the following functions:
Measurement of vacuum in the space between pipes with MKS-925 sensors;
Measurement of vacuum or overpressure in the inner (mesitylene) pipe by the MKS-901
sensor;
Display of data from thermocouples for temperature control;
Graphic image of temperature change;
Control of changes in gas blower speed;
Helium level control in a gas tank;
Monitoring of the passage of mesitylene pellets;
Gas flow control;
Periodic display on the screen of measuring and control devices;
Sound and text alarm in case of emergency.</p>
      <p>The user can set a measurement interval (from 2 to 5 seconds) and parameters for saving data
to a file.</p>
    </sec>
    <sec id="sec-4">
      <title>4. Results</title>
      <p>According to the results of operation and modernization of the cold moderator, the number of
hardware failures in the operation of the moderator is planned to be reduced by 50% and software
failures - by 80%.</p>
      <p>At present, work is underway to integrate the FANUC robot-repackler and a video control system
for its manipulations into the six-axis robot control system. The operator only needs to click on the
program button on the robot control tab and study the robot operating.</p>
    </sec>
    <sec id="sec-5">
      <title>5. Perspectives</title>
      <p>The main promising area of modernization of the cold moderator control system is the refusal
of using a PC as a means of control in favor of the Programmable Logic Controllers (PLC). The
operator’s PC will carry out only the function of an external user interface and a server for remote
control of the moderator parameters. This will increase the reliability of the system and its security
against unauthorized interference and exposure.</p>
    </sec>
  </body>
  <back>
    <ref-list>
      <ref id="ref1">
        <mixed-citation>
          [1]
          <string-name>
            <given-names>E. P.</given-names>
            <surname>Shabalin</surname>
          </string-name>
          . Сold neutron moderators //Physics of Elementary Particles and
          <string-name>
            <given-names>Atomic</given-names>
            <surname>Nuclei</surname>
          </string-name>
          .
          <article-title>-</article-title>
          <year>2005</year>
          . - Vol.
          <volume>36</volume>
          , part 6. - pp.
          <fpage>1425</fpage>
          -
          <lpage>1444</lpage>
          .- ISSN:
          <fpage>0367</fpage>
          -
          <lpage>2026</lpage>
          .
        </mixed-citation>
      </ref>
      <ref id="ref2">
        <mixed-citation>
          [2]
          <string-name>
            <surname>V. D.</surname>
          </string-name>
          <article-title>Anan'ev a.o. A test setup for the bead cryogenic neutron moderator of the IBR-2 reactor / A. A</article-title>
          .
          <string-name>
            <surname>Lyubimtsev</surname>
            ,
            <given-names>K. A.</given-names>
          </string-name>
          <string-name>
            <surname>Mukhin</surname>
          </string-name>
          , T. B.
          <string-name>
            <surname>Petukhova</surname>
            ,
            <given-names>A. P.</given-names>
          </string-name>
          <string-name>
            <surname>Sirotin</surname>
            ,
            <given-names>A. N.</given-names>
          </string-name>
          <string-name>
            <surname>Fedorov</surname>
            ,
            <given-names>E. P.</given-names>
          </string-name>
          <string-name>
            <surname>Shabalin</surname>
            ,
            <given-names>D. E.</given-names>
          </string-name>
          <string-name>
            <surname>Shabalin</surname>
            , and V. K. Shirokov //Instruments and
            <given-names>Experimental</given-names>
          </string-name>
          <string-name>
            <surname>Techniques</surname>
          </string-name>
          .
          <article-title>-</article-title>
          <year>2013</year>
          . -Vol.
          <volume>56</volume>
          , No. 1. - pp.
          <fpage>116</fpage>
          -
          <lpage>122</lpage>
          . - ISSN:
          <fpage>0020</fpage>
          -
          <lpage>4412</lpage>
          .
        </mixed-citation>
      </ref>
      <ref id="ref3">
        <mixed-citation>
          [3]
          <string-name>
            <given-names>A. S.</given-names>
            <surname>Kirilov</surname>
          </string-name>
          <article-title>a.o. An Arrangement of the Remote Control of Spectrometers on the IBR-</article-title>
          2M
          <string-name>
            <surname>Reactor</surname>
            / S. Kirilov,
            <given-names>S. M.</given-names>
          </string-name>
          <string-name>
            <surname>Murashkevich</surname>
            ,
            <given-names>R.</given-names>
          </string-name>
          <string-name>
            <surname>Yu</surname>
            . Okulov, and T. B. Petukhova //Instruments and
            <given-names>Experimental</given-names>
          </string-name>
          <string-name>
            <surname>Techniques</surname>
          </string-name>
          . - Vol.
          <volume>52</volume>
          , No. 1.- pp.
          <fpage>37</fpage>
          -
          <lpage>42</lpage>
          . - ISSN:
          <fpage>0020</fpage>
          -
          <lpage>4412</lpage>
          .
        </mixed-citation>
      </ref>
    </ref-list>
  </back>
</article>