       Attacking IEC 60870-5-104 Protocol∗

                       Péter György, Tamás Holczer

             CrySyS Lab, Department of Networked Systems and Services,
                  Budapest University of Technology and Economics
                                pgyorgy@crysys.hu
                                holczer@crysys.hu

       Proceedings of the 1st Conference on Information Technology and Data Science
                           Debrecen, Hungary, November 6–8, 2020
                               published at http://ceur-ws.org



                                        Abstract
         IEC 60870-5-104 is a widely used protocol for telecontrol in European
      power systems. Despite its wide usage, security was not a priority when
      the protocol was created in 2000. The IEC-104 protocol lacks important
      security features such as encryption, integrity protection, or authentication.
      In this paper, our goal is to show the risks of using this insecure protocol.
      To demonstrate it, we designed and implemented a wide range of different
      attacks. We also rated the stealthiness of these attacks in order to show that
      detection of an intruder is not always obvious. Our stealthy and successful
      attacks were carried out in a test environment with several virtual machines
      running an open-source implementation of the protocol.
      Keywords: IEC-104, attack, security, power grid


1. Introduction
IEC 60870-5-104 (a.k.a IEC-104) is part of the IEC 60870 set of standards [1].
IEC 60870 defines how telecontrol systems work in power transmission and control
applications.
Copyright © 2021 for this paper by its authors. Use permitted under Creative Commons License
Attribution 4.0 International (CC BY 4.0).
   ∗ This work was partially performed in the frame of the FIEK_16-1-2016-0007 project, im-

plemented with the support provided from the National Research, Development and Innovation
Fund of Hungary, financed under the FIEK_16 funding scheme.


                                            140
    IEC 60870-5-101 (a.k.a IEC-101) is a standard for power system monitoring,
control, and associated communications for telecontrol, teleprotection, and asso-
ciated telecommunications for electric power systems. IEC-104 protocol is an ex-
tension of the IEC-101 protocol with the changes in transport, network, link, and
physical layer services to suit the complete network access. The standard uses
TCP/IP. The application layer of IEC-104 is preserved the same as that of IEC-
101 with some of the data types and facilities not used.
    The security of IEC 104, by design, has been proven to be problematic. Though
the IEC technical committee has published a security standard IEC 62351, which
implements end-to-end encryption which would prevent such attacks as a replay,
man-in-the-middle (MitM), and packet injection. Unfortunately, due to the in-
crease in complexity vendors are reluctant to roll this out on their networks. The
insecure IEC 104 designed in the ’90s is still used widespread in European power
systems.
    In this paper, our goal was to show the possible consequences of using an inse-
cure protocol with known flaws.
    The remainder of this paper is organized as follows. Section 2 provides a brief
introduction to the IEC-104 protocol. Section 3 presents the overview of already
existing attacks against the protocol. Section 4 describes the architecture of our
simulator. In Section 5 the attack scenarios are described in detail. In Section 6
the attacks are evaluated. Finally, in Section 7 we summarize our work.


2. IEC 60870-5-104
As we have mentioned earlier IEC-104 is widely used for telecontrolling in Europe.
DNP3 is used for the same purpose in North America. This paper focuses on the
former protocol. IEC-104 follows the client-server architecture. The protocol has 2
message types APCI (Application Protocol Control Information) and ASDU (Ap-
plication Service Data Unit). In the following, we will give a brief overview of these
message types, to make understanding of the attacks easier. An in-depth analysis
of IEC-104 was published by Petr Matoušek [5], which describes the protocol in
more detail.


2.1. Application Protocol Control Information
Each APCI (Application Protocol Control Information) starts with a start byte
with value 0x68 followed by the 8-bit length of APDU (Application Protocol Data
Unit) and four 8-bit control fields(CF). APDU contains an APCI or an APCI with
ASDU. Generally, the length of the APCI is 6 bytes.
    The frame format is determined by the two last bits of the first control field.
The standard defines three frame formats, I-format, U-format, and S-format. The
S and I format stores the sequence numbers about the messages sent. If this counter
is invalid then the connection is terminated, this behaviour will be used in one of
the attacks. Figure 1 shows the structure of different frames.

                                         141
                       Figure 1. The frame formats of APCI.


2.2. Application Service Data Unit
The ASDU contains two main sections: the data unit identifier and the data itself.
It starts with a type of identification, which specifies the command. It also stores
the address of the originator. The information object address and the information
element (value).
    The information object address (IOA) is used as a selector, this specifies which
object we need to interact with. It is a 3 bytes long address. The information
element is a 2-byte long integer value, it stores the value of the IOA.
    There are 127 different messages used in IEC-104. There are commands for both
monitoring and controlling. When a server receives a command from the client, it
responds with the values requested by the client or by an acknowledgment. Figure 2
shows the structure of the ASDU.




                         Figure 2. The structure of ASDU.

   The APCI lacks integrity protection therefore tampering with the packet will

                                        142
not be noticed by the communicating parties. The lack of integrity protection will
be abused by several attacks described in Section 5.


3. State of the Art
The security of power systems is a well-researched topic [4, 11]. The security of
IEC-104 lead to numerous publications. There are papers about attacking the
protocol, hardening the protocol, and detecting attacks in networks where IEC-104
is used.


3.1. Flaws of the Protocol
Numerous flaws are described in [9]. The authors of the paper tried DoS attacks and
exploited the lack of authentication of the IEC-104 protocol. They also successfully
carried out a MitM attack where they could isolate the PLC and the MTU by
dropping packages.
    A more in-depth attack is described in [8]. The writers of the paper simu-
lated a complete attack from penetrating the SCADA to injecting packet in the
IEC communication. They reset the original connection and initiated a persistent
connection for the attacker.
    A very detailed description of MitM attacks is presented in [6]. The creators of
the paper tried packet replay attacks and packet modification attacks.
    During our research we used techniques from the previously mentioned papers.
The attacks described in these papers are fairly easy to detect because each of the
attacks reset the TCP stream. We wanted to avoid detection therefore we used more
stealthy methods to achieve full control over the power grid. Therefore, instead of
restarting the TCP stream like the authors of the mentioned papers, we achieved
the MitM position without terminating the original connection. This method is
far harder to notice since no log messages were generated by the communicating
parties unlike the attacks described in the mentioned papers.
    Before introducing our attack toolkit, we introduce the testbed we used in our
work.


4. Architecture of the Testbed
To test the security aspects of IEC-104, we required an implementation of the
protocol. The possible candidates were the following.

   • MasterOPC - IEC-104 [7]

   • OpenMUC - IEC-104 [2]

   • FreyrSCADA - IEC-104 [3]

                                        143
    Out of the three candidates, we decided to work with the OpenMUC imple-
mentation of the protocol. The main reason behind the decision was that the
implementation is open-source and it was written in Java, therefore it can be cus-
tomized to fit our needs.
    As we have mentioned earlier in Section 2 the protocol follows the client-server
architecture. Therefore we need two machines, one of them for the client and the
other one for the server. We also wanted to test MitM attacks, therefore we put in
a router machine between the client and the server. The machines were virtualized
in vCenter. The network architecture is presented in Figure 3.
    We assume that the attacker already penetrated the network where IEC-104 is
used, but neither the servers nor the clients are exploited. The attacker is present in
the network with a device which can put itself in the middle of the communication.
This kind of attacks are well known from the past, thus not described in this paper.
The interested reader can understand the basics of such attacks from various sources
such as [10].




                   Figure 3. IEC Network where attacker is inside.


                                         144
   We designed a small power grid with a few stations. This grid was controlled
by the IEC client. The topology of the grid is presented in Figure 4.




                      Figure 4. The topology of the stations.

   The client periodically sends control commands to the server to generate net-
work traffic.
   For better visualization, we created a small web app, that holds the value of
each station, the app is presented in Figure 5.




                    Figure 5. The visualization of the stations.

    As the main components of the test environment is introduced, we may proceed
to the attacks against the protocol.


5. Attacking the Protocol
In this section, we introduce the attacks. The attacks we designed vary in severity
and complexity. We will start with simple attacks, and move forward to more
complex scenarios.

                                        145
5.1. Unauthorized Access
The protocol lacks authentication therefore an attacker can connect to a server and
send commands. For example, an attacker could send an interrogation command
to learn the IOAs used by the server. The steps of the attacks are the following:

   • Discover the IP address and port of the IEC Server.

   • The attacker has to impersonate an IEC Client and send a connection request
     to the IEC Server.

   • Since the protocol lacks authentication, the connection request of the attacker
     will be accepted.

   • The attacker can send arbitrary commands to the IEC Server.

   Figure 6 shows the output of the IEC Server.




                   Figure 6. The log messages of the IEC Server.


    As it is shown in Figure 6 the IEC Server logs every connection, therefore it is
fairly easy for an operator to detect unauthorized access attacks if log analysis is
done properly.


5.2. Tampering with IEC APCI Sequence Numbers
An unexpected sequence number in the APCI field of the packet results in the
termination of the connection. This behavior can be used to cause Denial of Service
(DoS). An attacker with Man in the Middle (MitM) capabilities can exploit this
behavior using the following steps:

   • Pass the routing of packets to a user space program. For example, use Net-
     filterQueue1

   • Capture a packet

   • Modify the sequence number of the IEC APCI

   • Recalculate TCP checksum and modify it

   • Release the packet
  1 https://www.netfilter.org/projects/libnetfilter_queue/doxygen/html/




                                        146
Figure 7 shows the output of the IEC Server.




                  Figure 7. The log messages of the IEC Server.


   As it is shown in Figure 7 the IEC Server logs the unexpected sequence number,
therefore it is fairly easy for an operator to detect this attack.

5.3. Poison TCP Stream
The communication between the server and the client is carried out in a single
TCP stream which is constantly kept alive. If the attacker can modify or insert a
packet with an incorrect TCP sequence number, or send a FIN while impersonating
a valid party, then the communication is terminated. This behavior can be used
to cause DoS. An attacker with MitM capabilities can exploit this behavior using
the following steps:

   • Pass the routing of packets to a user space program. For example, use Net-
     filterQueue

   • Capture a packet

   • Modify the TCP sequence number and acknowledgment number

   • Recalculate TCP checksum and modify it

   • Release the packet

   Figure 8 shows the output of the IEC Server.




                  Figure 8. The log messages of the IEC Server.


                                      147
   As it is shown in Figure 8 the IEC Server logs the loss of connection but does
not log the reason, therefore it is much harder for an operator to detect this attack.

5.4. Packet Injection
An attacker can inject packets to the communication, however simply injecting
a packet will result in the termination of the connection, because it will cause a
sequence number (both APCI and TCP) miss-match between the server and the
client. Therefore after injecting a packet the attacker needs to patch the sequence
number of every other packet. Not just the sequence number can be modified but
also the values of the ASDU field. Therefore, this can lead to taking over the
control of the power grid. An attacker needs to be in a MitM position to carry out
this attack. The steps of the attack are the following:

   • Pass the routing of packets to a user space program. For example, use Net-
     filterQueue.

   • Read every packet that passes through and learns the TCP and IEC sequence
     numbers (Learning Phase).

   • As the attacker learned every sequence number he can inject a new packet to
     the communication (Inject Phase).

   • Keep track of the sequence numbers using sequence number offsets.

   • Capture every other packet and patch the sequence numbers so the connection
     will not terminate due to incorrect sequence numbers (Patch Phase).

   Figure 9 shows the visual representation of the attack, it is important to note
that in “Patch Phase” the attacker has to correct the sequence number, to avoid
termination of connection and therefore be detected.
   This attack is much harder to detect because the connection is not terminated.
The attacker can spoof the values that are seen by the operator, which makes
detecting even harder.


6. Evaluation
The difficulty of detection and the severity of the attacks described in Section 5 is
different.
    The attack described in Section 5.1 has a very high severity because the attacker
can send arbitrary commands to the server. The attack does not require a skilled
attacker, which makes it even more dangerous. The operator and the attacker are
simultaneously controlling the stations. New connections are logged by the server
therefore it is easy to detect this attack.
    The attacks described in Section 5.2 and 5.3 are similar. The severity of these
attacks is medium because they can prevent the client from controlling the server.

                                         148
                   Figure 9. Flow of the packet injection attack.



However, these attacks can be used combined with the attack described in Sec-
tion 5.1 to hinder the operator even more.
    The attack described in section 5.4 has a critical severity because the attacker
can send arbitrary commands and can also stop the client from communicating with
the server. The attacker can also spoof values for the client, to make the operator
believe everything is working properly. No log message is generated during this
attack, therefore the detection is also hard.


7. Summary and Future Works
We created numerous attacks against the IEC-104 protocol. Our goal was to show
that even an attacker with limited skills can cause severe damage in a network
where an insecure protocol is used. The possible consequences can range from DoS
attack to complete takeover of the power grid.
    In our opinion, it worth the extra complexity to switch to the secure variant
of the protocol because using the insecure version can lead to unnecessary harmful
events.

                                        149
   If an attacker wants to get full control over the grid, he also requires the IOA
and Station ID pairs. Without the pairs, the attacker can just blindly send control
and monitor command to the IOAs, without exactly knowing what he is doing.
With the pairing, the attacker can precisely target his commands to manipulate
the power grid in his own will. To achieve a full control attack scenario we are
working on an algorithm that can pair the Station IDs to the corresponding IOAs.
   The attacks which are introduced in this paper were carried out in a simulator.
We also want to test in a real-world environment in the near future.

Acknowledgements. We want to thank Csatár János from BME VET for help-
ing us with the simulator.


References
 [1] IEC: Part 5-104: Transmission protocols – Network access for IEC 60870-5-101 using stan-
     dard transport profiles (Second Edition), International Electrotechnical Commission, 2006.
 [2] IEC 60870-5-104, https://www.openmuc.org/iec-60870-5-104/.
 [3] IEC 60870-5-104 Master Client Simulator, http://www.freyrscada.com/iec- 60870- 5-
     104-Client-Simulator.php.
 [4] W.-W. Li, W.-X. You, X.-P. Wang: Survey of cyber security research in power system,
     Power System Protection and Control 39.10 (2011), pp. 140–147.
 [5] P. Matoušek: Description and analysis of IEC 104 Protocol, Faculty of Information Tech-
     nology, Brno University of Technology, Tech. Rep (2017).
 [6] P. Maynard, K. McLaughlin, B. Haberler: Towards understanding man-in-the-middle
     attacks on iec 60870-5-104 scada networks, in: 2nd International Symposium for ICS &
     SCADA Cyber Security Research 2014 (ICS-CSR 2014) 2, 2014, pp. 30–42.
 [7] OPC Client for IEC 60870-5-104, https://https://www.opcti.com/iec- 60870- 5- 104-
     scada-master.aspx.
 [8] Q. S. Qassim, N. Jamil, M. Daud, N. Ja’affar, S. Yussof, R. Ismail, W. A. W. Ka-
     marulzaman: Simulating command injection attacks on iec 60870-5-104 protocol in scada
     system, International Journal of Engineering & Technology 7.2.14 (2018), pp. 153–159.
 [9] P. Radoglou-Grammatikis, P. Sarigiannidis, I. Giannoulakis, E. Kafetzakis, E.
     Panaousis: Attacking IEC-60870-5-104 SCADA Systems, in: 2019 IEEE World Congress
     on Services (SERVICES), vol. 2642, IEEE, 2019, pp. 41–46.
[10] T. M. Thomas, D. Stoddard: Network Security First-Step, Cisco Press, 2011.
[11] W. Wang, Z. Lu: Cyber security in the smart grid: Survey and challenges, Computer
     networks 57.5 (2013), pp. 1344–1371.




                                             150