<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Archiving and Interchange DTD v1.0 20120330//EN" "JATS-archivearticle1.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <journal-meta />
    <article-meta>
      <title-group>
        <article-title>Intelligent Control of Industrial Compensating Devices Based on the Application of Fuzzy Logic</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>Andrey Kupin</string-name>
          <email>kupin.andrew@gmail.com</email>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <contrib contrib-type="author">
          <string-name>Yurii Sherstnov</string-name>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <contrib contrib-type="author">
          <string-name>Yuriy Osadchuk</string-name>
          <email>u.osadchuk@knu.edu.ua</email>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <contrib contrib-type="author">
          <string-name>Olexander Savytskyi</string-name>
          <email>savytskyi@knu.edu.ua</email>
          <xref ref-type="aff" rid="aff0">0</xref>
        </contrib>
        <aff id="aff0">
          <label>0</label>
          <institution>Kryvyi Rih National University</institution>
          ,
          <addr-line>Vitaly Matusevich 11, Kryvyi Rih, 50027</addr-line>
          ,
          <country country="UA">Ukraine</country>
        </aff>
      </contrib-group>
      <pub-date>
        <year>1807</year>
      </pub-date>
      <abstract>
        <p>The process of reactive power compensation has been formalized using the example of daily electricity consumption by the power substation of the enterprise. The choice of the fuzzy control principle for the operation of compensating devices is justified. Results of computer modeling of the reactive power compensation process based on actual electricity consumption data from powerful substations of the mining and beneficiation plant are presented. The effectiveness of using the fuzzy control principle for compensating devices has been analyzed. The experimental data from January and June 2019 for one of the main substations of the enterprise were used by the authors for testing. The proposed algorithm for controlling the compensation process is implemented based on fuzzy control. Mining and beneficiation plants, fuzzy logic, power networks, energy efficiency, filterORCID: : 0000-0001-7569-1721 (A. Kupin); 0009-0003-3210-5552 (Y. Sherstnov); 0000-0001-6110-9534 (Y. Osadchuk); 0000-0002-8904-</p>
      </abstract>
    </article-meta>
  </front>
  <body>
    <sec id="sec-1">
      <title>-</title>
      <p>compensating devices, synchronous motors, algorithm.</p>
    </sec>
    <sec id="sec-2">
      <title>1. Introduction</title>
      <p>Modern electricity consumers at the mining and metallurgical complex stations often have
nonlinear load characteristics. The presence of semiconductor converters in them and other areas of the
enterprise leads to a deterioration in the quality of power supply due to the emergence of higher
harmonic components of voltage and current, as well as other indicators [7]. As a result, the equipment
wears out faster, and electricity costs may increase due to additional payment for reactive power [21].
Thus, the network operator is forced to implement measures to compensate for reactive power [5, 6].
However, due to the uncertainty of the load and disturbances, compensating systems require more
complex approaches to implementation at the design stage. A system based on fuzzy logic can
implement such control.</p>
      <p>This paper focuses on the substations of the mining and beneficiation complex as the object of
research. The subject of the research is the system of control with compensating devices based on fuzzy
logic. The main feature and, at the same time, advantage of this system is:</p>
      <p>Fuzzy control allows working with fuzzy input data, which is useful when dealing with complex
systems. For example, as in our case, substations with a large number of electricity consumers.</p>
      <p>The use and configuration of controllers based on fuzzy logic is more intuitive and simple to
set up based on expert rules.</p>
      <p>However, we need to consider certain factors to determine such rules. Therefore, the article solves
the problem of choosing rational scientific approaches to creating a rational control system for the
reactive power compensation process [6].</p>
      <p>As an example, an analysis of reactive power consumption during the summer and winter months is
presented. The effectiveness of the operation of compensating devices (CDs) using arbitrary daily
EMAIL:
(Y. Sherstnov);</p>
      <p>2023 Copyright for this paper by its authors.
reactive power consumption is investigated. Numerous studies by the authors [1-2] have convincingly
shown that improving energy efficiency and reducing the cost of the enterprise is possible through the
implementation of an automatic control algorithm. The implementation of a process for determining
energy-efficient control with parallel use of CDs and synchronous motors (SMs) is proposed. Despite
the considerable amount of research in this field, a number of issues require constant clarification and
adaptation to the conditions of a specific enterprise [16-17]. This applies to the preliminary analysis of
reactive power consumption levels and the possibility of including SMs in the compensation process.
Thus, this work will consider a method of controlling compensating devices based on fuzzy control and
mathematical models based on real energy consumption data.
2. Control algorithm for compensating devices and its implementation based
on fuzzy</p>
      <p>An effective solution in the case of powerful consumers with non-linear loads on the network is the
installation of filter-compensation devices (FCDs). The main goal of FCD implementation is to reduce
the harmonic composition and control the load tangent of the object at a level of tgφ&lt;0.25 [21].
Typically, powerful enterprises have SMs in their assets, which can also be involved in the reactive
power compensation process [10]. The level of reactive power generation is determined by changing
the excitation current. However, a significant increase in the excitation current may lead to overheating
and premature failure of the motor. Therefore, to ensure rational control of the excitation current, it is
advisable to develop a set of rules for monitoring the temperature of the windings.</p>
      <p>Figure 1 shows the structure of an automated control system for the excitation of SMs and the
switching of FCDs for reactive power compensation within the enterprise network to balance its flows
between consumers (AM, transformers) and from FCDs and SMs. The directions of the reactive power
flows are also indicated in Figure 1.</p>
      <p>On Figure 1: AECS - Automatic excitation control system; SDRP CS - Systems of automatic control
of reactive power; ASCS FCD - Automatic system of automatic control of stages of the FCD.</p>
      <p>To reduce the impact of reactive power on the power grid, an algorithm for compensating reactive
power is proposed. This algorithm involves the installation of reactive power compensators. The use of
the reactive power compensation algorithm allows for a reduction in energy consumption costs,
increased efficiency and reliability of the power grid, reduced risk of overvoltage and equipment
overload, as well as a decrease in energy losses in the network.</p>
      <p>The process control scheme for reactive power compensation can be implemented using the
algorithm shown in Figure 2. It should be noted that the algorithm first analyzes the compensating
powers of capacitor installations, as losses in kW/kVAR for capacitor banks typically range from
0.0020.0045, whereas for synchronous motors, this value is 0.013 kW/kVAR for our conditions and existing
parameters, consistent with overall evaluation trends. Therefore, the most favorable compensation
process is the involvement of capacitor installations in the first place.
the third degree is introduced, etc.</p>
      <p>if Q2FCD&gt;Q or QiFCD&lt;Q&lt; Qi+1FCD , then there is an adjustment of the residual reactive power from the
compensation of the synchronous motor:
(3)
(4)
(5)</p>
      <p>The availability and possibility of SM for compensation is checked QSM. It is distributed
between the synchronous motors involved in the compensation.</p>
      <p>There is a constant check:
3.
value:

−</p>
      <p>→  
 &gt;   +1</p>
      <p>+  
 −  
+   +1
=  
if so, an i+1 step of FCD is introduced, with the setpoint of the regulating SM directed to the next
Q`SM distributed between SM, providing Si*=const. If the FKP capabilities are exhausted, then the
process is implemented exclusively with the help of synchronous motors.</p>
      <p>ACRP devices (automatic control reactive power) and controllers based on fuzzy logic can be used
for controlling the reactive power compensation process. However, they have some differences in usage
and operating principles.</p>
      <p>The main difference between ACRP and fuzzy logic controllers is that ACRP use precise (crisp)
algorithms for controlling the reactive power compensation process, whereas fuzzy controllers use
fuzzy algorithms. ACRP have built-in precise algorithms that provide automatic switching on and off
of capacitors depending on the level of reactive power in the electrical network. ACRP can also switch
capacitors on and off depending on the voltage and current levels in the network to ensure optimal
reactive power compensation.</p>
      <p>Fuzzy controllers use fuzzy logic to control the process of reactive power compensation. These
controllers allow for a wider range of factors that affect the compensation process to be taken into
account, such as the state of the network, the level of harmonics, the instability of the power supply,
and so on. This provides a more flexible and effective management of reactive power compensation.
compensation. Therefore, the principles of fuzzy control can be used for automatic regulation of reactive
power compensation with capacitor banks, which will provide more precise and efficient compensation.</p>
      <p>After analyzing the data for the winter and summer months, the necessary "base level" of
compensating ability was determined to be 7500 kVAr·h. Since the level of reactive power consumption
below this value is not normal, this only occurs in the case of disconnecting powerful consumers (for
example, one or two lines of consumption of the OBF1). After that, the consumption of reactive power
was calculated taking into account the base level. To determine the rational capacities of capacitor
banks, a law of normal distribution was compiled (see Figure 4). On the graph, it can be seen that the
maximum for January corresponds to 750 kVAr·h, the highest common point is 1500 kVAr·h, and the
third is 2250 kVAr·h. Thus, three levels of reactive power consumption can be determined as input
parameters for the fuzzy controller.
the necessary power factor and efficient operation of the motor.</p>
      <p>According to [16, 17], the maximum value of the total power of motors participating in reactive
power compensation mode can be determined:

where tcr̊ is the maximum permissible temperature of the cooling air. Un is rated voltage of the motor.
∆tcr̊ is the maximum allowable temperature exceedance of the stator windings.</p>
      <p>The temperature of a synchronous motor can be used as an additional parameter for controlling the
excitation current. An increase in temperature can indicate motor overload or other issues that require
controller action. The use of fuzzy control allows for a system that can automatically adjust excitation
current based on motor temperature.</p>
      <p>Considering the load on the synchronous motor is also an important factor in reactive power
compensation, as it can affect its operation and compensation efficiency. In particular, a change in load
on the synchronous motor leads to a change in power consumed, and therefore, a change in reactive
power. If load changes are not taken into account during reactive power compensation,
overcompensation or undercompensation of reactive power may occur.</p>
      <p>One can express the loading of a synchronous motor as a percentage of its rated power because the
rated power is the fundamental value used to determine the motor's maximum efficiency. Therefore,
information about the loading of a synchronous motor is an important parameter for determining its
efficiency and monitoring its operation.</p>
      <p>It is also necessary to consider the number of motors that can participate in the compensation process
and their loading. In particular, when the active load SM changes, its compensating ability for reactive
power also changes, which should be taken into account. If several SMs of different or the same rated
power are involved in the regulation of reactive power, it is necessary to ensure their equal relative
loading in terms of full power.</p>
      <p>= √  2 +  2 = 
(7)</p>
      <p>It is also important to consider the number of motors that can participate in the compensation process
and their load. This, in turn, can affect the overall ability to compensate reactive power using SM. The
presence of a large number of motors allows for smoother distribution of compensation levels by
including motors with low loads and/or no overheating in the compensation process.
3. Research on the effectiveness of proposed methods</p>
      <p>To investigate the effectiveness of fuzzy control compensating devices, the following steps will be
taken:</p>
      <p>1. Create and configure a fuzzy controller that will make decisions about compensating reactive
power based on input data about the state of the electrical network.</p>
      <p>2. Evaluate the effectiveness of the reactive power compensator with fuzzy control based on
experimental data on daily power consumption.</p>
      <p>The calculation of the fuzzy regulator will be carried out using the FuzzyLogicToolbox Matlab
package.</p>
      <p>To do this, we will select input parameters that affect the compensating ability of the fuzzy
controller, as shown in Figure 5. First, there is the parameter of reactive power consumption (Qcons),
with levels of consumption being low, medium, and high. The second parameter is tgφ. The next
parameter is the number of SMs in the network, as well as the temperature and load of the motors. These
three parameters have a significant impact on the amount that we can compensate using SMs. However,
when a synchronous motor is highly loaded, its temperature is usually higher than nominal. This is
because as the load on the motor increases, its power loss from resistances caused by losses in the stator
and rotor, as well as losses due to magnetization, increases. This leads to an increase in the motor's
temperature. If the motor's temperature remains low under high load, this may be a sign of ineffective
operation or an emergency state. Therefore, it is advisable to combine the load and temperature
parameters.</p>
      <p>All important conditions were taken into account during construction. For example, synchronous
motors cannot fully participate in reactive power compensation at high temperature and high load. This
is done to prevent emergencies. It is important to monitor the temperature of the synchronous motor
during operation to avoid overheating and equipment damage. Temperature sensors can be used to
monitor the motor temperature and take measures to reduce it if necessary. For example, with higher
values of SM quantity in the network, we can use their share of compensating capacity. This is done by
distributing the necessary reactive power that needs to be compensated among all the motors.</p>
      <p>Figure 6 shows membership functions that were chosen for input parameters (a, b, c, d) and output
compensation capability value (e). The membership functions correspond to the following parameters:
a - input reactive power consumption value; b - tanφ value in the network; c - number of synchronous
motors; d - motors' temperature and load; e - output value of the function. Taking into account all the
aforementioned factors, the following dependencies were obtained (Figure 7, 8).
determine the latter. One can use this tool to efficiently tune the parameters of the fuzzy controller and
ensure its optimal performance [5]. In this case, we can see that regardless of the reactive power
consumption, tanφ, the number of SMs, and their loading, we are able to fully compensate for this
quantity. Thus, the composed set of rules allows for effective compensation of reactive power.</p>
      <p>Figure 10 and Figure 11 depict the results of the reactive power compensation algorithm using CD
and SM for a day in January and June, respectively.
compensated bysynchronousmotors.</p>
      <sec id="sec-2-1">
        <title>Q (Consumption), kVAr*h (January)</title>
      </sec>
      <sec id="sec-2-2">
        <title>Connected step, kVAr*h</title>
      </sec>
      <sec id="sec-2-3">
        <title>Q comp. SM 1, kVAr*h</title>
      </sec>
      <sec id="sec-2-4">
        <title>Q comp. sum, connected step, kVAr*h</title>
      </sec>
      <sec id="sec-2-5">
        <title>Q comp. SM 2, connected step, kVAr*h</title>
        <p>Figure10:Reactivepowercompensationusingcapacitorbanksandsynchronousmotors.January.</p>
        <p>Q, kVAr*h
1600
1400
1200
1000
800
600
400
200</p>
        <p>0
-200
3000
Q, kVAr*h
2500
2000
1500
1000
500
0</p>
      </sec>
      <sec id="sec-2-6">
        <title>Q comp. sum, connected step, kVAr*h</title>
      </sec>
      <sec id="sec-2-7">
        <title>Q comp. SM 2, connected step, kVAr*h</title>
        <p>Figure11:Reactivepowercompensationusingcapacitorbanksandsynchronousmotors.June.</p>
        <p>However, the process of transient phenomena when using SMs and FCDs for reactive power
compensation is also important. The article explores their compensation potential specifically from the
perspective of reactive power generation levels. Transient processes when using synchronous motors
and capacitor banks for reactive power compensation depend on several factors [17].</p>
        <p>Firstly, they depend on the parameters of the synchronous motor itself, such as its capacitance,
resistance, and inductance. These parameters affect the motor's response time to load changes and the
effectiveness of reactive power compensation. Secondly, transient processes depend on the properties
of capacitor banks, such as their capacitance, voltage, and frequency. These parameters affect the
effectiveness of reactive power compensation and the stability of the network [18]. Thirdly, transient
processes depend on the characteristics of switching devices, such as switching time and resistance.
These parameters affect the speed of current and voltage changes.</p>
        <p>Therefore, studying transient processes is important for evaluating the effectiveness of reactive
power compensation and the stability of the network, but depends on many factors, including the
parameters of synchronous motors and capacitor banks, as well as the characteristics of switching
devices [13]. Therefore, the use of compensation devices with the specified values in the control system
requires further research.</p>
        <p>Analyzing the obtained data, it can be stated that the implementation of the compensation algorithm
using the proposed method will allow the company with a total installed active power of 283 MW to
reduce the payment for reactive power from approximately 400,000 hryvnias per month to one thousand
hryvnias per month. Of course, the proposed method only takes into account payment for reactive power
according to the tariff. If the payback period of implementation is taken into account, it will depend on
many factors, where one of the main ones will be the method of implementation of this method.
Therefore, the payback period of implementation of the KP control algorithm should be calculated on
an individual basis.</p>
      </sec>
    </sec>
    <sec id="sec-3">
      <title>4. Conclusion</title>
      <p>Based on statistical data on reactive power consumption of the power substations at PJSC
"NorthMEP", a method for selecting the power of compensating devices to ensure minimum payment
for reactive power by the enterprise has been proposed. The proposed system of automatic control of
compensating devices (by switching FCDs) and regulation of excitation of synchronous motors (for
reactive power compensation) balances the flow of reactive power between consumers (asynchronous
motors, transformers, etc.), with control of technological parameters of synchronous motors [12]. The
developed algorithm is implemented based on fuzzy logic with the consideration of important
technological parameters. The obtained level of compensating possibilities depends on all the
considered parameters. According to the results of graphical representations, the required level of
compensation ensures high energy efficiency.
5. References
[1] A. Kupin, Yu. Osadchuk, O. Savytskyi, Yu. Sherstnоv, Enhancement of the voltage supply quality
of substations at mining and processing plants, Scientific Notes of Tavria National University
named by V.I. Vernadsky, vol. 33 (72), no. 4 (2022) 149–159. doi:
10.32838/26635941/2022.4/23.
[2] V. Verbynets, Yu. Sherstnov, S. Silchenko, A. Kupin, Yu. Osadchuk, O. Savytskyi, Control
algorithm of filter-compensating devices under the conditions of the presence of synchronous
motors, Scientific Notes of Tavria National University named by V.I. Vernadsky, vol. 34 (73), no.
1 (2023) 173-179. doi: 10.32782/2663-5941/2023.1/26.
[3] A. Bublikov, V. Tkachov, Automation of the control process of the mining machines based on
fuzzy logic, Naukovyi Visnyk Natsionalnoho Hirnychoho Universytetu, vol. 3 (2019) 112–118.
doi: 10.29202/nvngu/2019-3/19.
[4] E. Zharikov, S. Telenyk, O. Rolik, Method of Distributed Two-Level Storage System
Management in a Data Center Advances in Intelligent Systems and Computing, Advances in
Computer Science for Engineering and Education II, (2020) 301–315.
doi:10.1007/978-3-03016621-2_28.
[5] A. Binbusayyis, Deep embedded fuzzy clustering model for collaborative filtering recommender
system, Intelligent Automation &amp; Soft Computing, vol. 33, no. 1 (2022) 501–513. doi:
/10.32604/iasc.2022.022239.
[6] F. Donghan, J. Shong, G. Deqiang, Reactive market power analysis using must-run induces, IEEE</p>
      <p>Transactions on Power Systems, vol. 23, no. 2 (2008) 755-765.2. doi: 10.1109/TPWRS.2008.919416.
[7] El-S. Ismael, B. Kankar, C. Claudio, A. Miguel, P. Jiuping, A Procurement market model for
reactive power services considering system security, IEEE Transactions on Power Systems, vol.
23, no. 1 (2008) 137-149. doi: 10.1109/TPWRS.2007.913296.
[8] M. Bornschlegl, M. Bregulla, J. Franke, Methods-Energy Measurement An approach for
sustainable energy planning of manufacturing technologies, Journal of Cleaner Production, vol.
1351 (2016) 644–656. doi: 10.1016/j.jclepro.2016.06.059.
[9] K. Biel, C. Glock, Systematic literature review of decision support models for energy-efficient
production planning, Computers &amp; Industrial Engineering, vol. 101 (2016) 243–259. doi:
10.1016/j.cie.2016.08.021.
[10] P. Moradi, S. Ahmadian, F. Akhlaghian, An effective trust-based recommendation method using
a novel graph clustering algorithm, Physica A: Statistical Mechanics and its Applications, vol. 436
(2015) 462–481. doi: 10.1016/j.physa.2015.05.008.
[11] J. Deng, J. Guo, Y. Wang, A novel k-medoids clustering recommendation algorithm based on
probability distribution for collaborative filtering, Knowledge-Based Systems, vol. 175 (2019)
96–106. doi: 10.1016/j.knosys.2019.03.009.
[12] J. Bobadilla, F. Ortega, A. Gutiérrez, S. Alonso, Classification-based deep neural network
architecture for collaborative filtering recommender systems, International Journal of Interactive
Multimedia &amp; Artificial Intelligence, vol. 6, no. 1 (2020) 68–77. doi: 10.9781/ijimai.2020.02.006.
[13] D. M. Oscar, G. Walter, Dynamic active and reactive power compensation in distribution networks
with batteries: A day-ahead economic dispatch approach, Computers &amp; Electrical Engineering,
vol. 85 (2020) 106710. doi: 10.1016/j.compeleceng.2020.106710.
[14] I. Czarnowski, J. Jędrzejowicz, P. Jędrzejowicz, Designing RBFNs Structure Using
SimilarityBased and Kernel-Based Fuzzy C-Means Clustering Algorithms, IEEE Access, vol. 9 (2021)
44114422. doi: 10.1109/ACCESS.2020.3048104.
[15] R. Kruse, S. Mostaghim, C. Borgelt, C. Braune, M. Steinbrecher, Computational Intelligence. A
Methodological Introduction, Springer Nature Switzerland AG, 2022, 639 p. doi:
10.1007/978-3030-42227-1.
[16] Z. Tan, L. He, An efficient similarity measure for user-based collaborative filtering recommender
systems inspired by the physical resonance principle, IEEE Access, vol. 5 (2017) 27211–27228.
doi: 10.1109/ACCESS.2017.2778424.
[17] B. Mohammed, S. Samer, T. Yuting, M. Joydeep, Reactive power compensation for reliability
improvement of power systems, in: IEEE/PES Transmission and Distribution Conference and
Exposition (T&amp;D), Dallas, TX, USA, 2016. doi: 10.1109/TDC.2016.7519910.
[18] H. Zarzour, Z. Al-Sharif, M. Al-Ayyoub, Y. Jararweh, A new collaborative filtering
recommendation algorithm based on dimensionality reduction and clustering techniques, in: Proc.
of the Ninth IEEE Information and Communication Systems (ICICS) Conf., Irbid, Jordan, 2018,
pp. 102–106. doi:10.1109/IACS.2018.8355449.
[19] W. Jiahui, M. Weishi, Z. Zhiyu, Short-Term Load Forecasting Based on GA-PSO Optimized
Extreme Learning Machine, in: 2nd IEEE Conference on Energy Internet and Energy System
Integration, 2018, Proceedings art. no. 8582545, doi: 10.1109/EI2.2018.8582545.
[20] Y. Xuan, Distributed state estimation with the measurements of phasor measurement units,
Master’s thesis, School of Electronic, Electrical and Computer Engineering, The University of
Birmingham, Birmingham, United Kingdom, 2013.
[21] On the approval of the Methodology for calculating the fee for the flow of reactive electricity:
order of the Ministry of Energy and Coal Industry of Ukraine, Feb. 6, 2018 no. 87. URL:
https://zakononline.com.ua/documents/show/374951___668077.
[22] Yu. Osadchuk, Yu. Sherstnоv, The method of increasing the energy efficiency of technical systems
of technological units with synchronous drives by adjusting their reactive power, 2020. Patent No.
141771, Filed November 17th., 2019, Issued April 27th., 2020.
[23] Yu. Osadchuk, Yu. Sherstnоv, Device for increasing the energy efficiency of technical systems of
technological units with synchronous drives, Patent No. 149078, Filed June 3rd, 2021, Issued
October 13th, 2021.</p>
    </sec>
  </body>
  <back>
    <ref-list />
  </back>
</article>